Product range  |  Lighting Energy Controller  |  Danfoss

Drives Center  |  Example

Energy savings achieved through variations in pump drive speed

Over 50% reduction in electricity consumption

Example with variable delivery over 1 year
This example was calculated using a 45 kW pump in an installation supplying variable delivery (see table) at an average of just over 200 m3/h.

Frequency converter control reduced annual electricity consumption by over 50%, from 275,064 kWh to 124,173 kWh.

The return on investment in this example is for a little over one year.
M3/h
Breakdown
Valve control
Frequency converter control
%
hours
kW
kWh
kW
kWh
350
5
438
42.5
18,615
42.5
18,615
300
15
1,314
38.5
50,589
29.0
38,106
250
20
1,752
35.0
61,320
18.5
32,412
200
20
1,752
31.5
55,188
10.0
17,520
150
20
1,752
28.0
49,056
6.5
11,388
100
20
1,752
23.0
40,296
3.5
6,132
Total
100
8,760
275,064
124,173

 

 Save electrical lighting energy without replacing your light fittings | Assess the potential savings on your lighting costs
Home Page | Contact | Print version | Send | Site map
Copyright by Lexen